收藏 分享(赏)

洲际酒店 消防安全设计标准(英)P30.ppt

上传人:空登山 文档编号:7032365 上传时间:2022-08-29 格式:PPT 页数:30 大小:10.21MB
下载 相关 举报
洲际酒店 消防安全设计标准(英)P30.ppt_第1页
第1页 / 共30页
洲际酒店 消防安全设计标准(英)P30.ppt_第2页
第2页 / 共30页
洲际酒店 消防安全设计标准(英)P30.ppt_第3页
第3页 / 共30页
洲际酒店 消防安全设计标准(英)P30.ppt_第4页
第4页 / 共30页
洲际酒店 消防安全设计标准(英)P30.ppt_第5页
第5页 / 共30页
亲,该文档总共30页,到这儿已超出免费预览范围,如果喜欢就下载吧!
资源描述

1、1Key Fire Life Safety Elements of the IHG Engineering Standards2Overview This presentation is aimed at providing key stakeholders associated with new hotel construction, hotel re-branding and hotel renovation an overview of the important and sometimes missed key Fire Life Safety elements of the IHG

2、Engineering Standards. The information contained in this presentation does not replace the need for those involved to read and understand the IHG Engineering Standards that affect the various elements of an IHG branded property. Your nearest IHG Corporate Technical Services office personnel are ther

3、e to provide you with any additional information and support you may require.3IHG Engineering Standards Fire Life SafetyThe key and most important section of theIHG Engineering Standards is:-Section 7Fire Life SafetyCompliance with this section is MANDATORY4IHG Engineering Standards Fire Life Safety

4、The IHG Fire Life Safety Standards have been developed as a result of :- Lessons learnt from previous hotel fires and emergency situations Customer attitude & expectations toward their fire life safety requirements Pressure from international companies & large corporations for hotels to provide safe

5、r lodgings for their employees (Ie. Airlines) Changes and improvements in local & international life safety standards5CompartmentationOften poorly executed and often cause delays in opening a hotel!6CompartmentationGood pipe collars but poor seal up7CompartmentationThe right product for the right jo

6、b. 8CompartmentationFire dampers are required wherever ducting passes through 2 hr (or higher) fire rated walls or floorsFire dampers must be easily accessible for regular testing & maintenance9CompartmentationFire doors must close properly10CompartmentationGuestroom doors 44mm solid core 20 min fir

7、e rated, self closing and latching (No hold open)M&E pipe shaft doors 1.5 hr fire rated11CompartmentationRAVEN BRAND FIRE / SMOKE PROOF DOOR SEALS To be fitted to all guest room doors12Detection & NotificationAFA system will be fully addressableGuestroom detectors must have a built in sounder (85dB

8、at the bed head)With mimic panel for telephone operators room13Detection & NotificationLoop fault monitoring:Class A wiring for initiating devices and evacuation speakers14Detection & NotificationGuestroom speakers 75dB at the bed headBack boxes for all evacuation speakers15Detection & NotificationE

9、vac system in 3 languages & capable of single or multi zone pagingAll BGM & audio systems shall be disabled when the AFA & Evac system activateBGM16Detection & NotificationStrobe lights, warning bells & manual break glass stations in public and back of house areas17Emergency EgressDead ends:-New Bui

10、lds max 9mRe-brand max 15m18Emergency EgressTwo means of escape for spaces designed to hold more than 50 people or that are greater than 75 sq m19Emergency EgressExit doors unlocked and swinging in the direction of travel20Emergency Egress- Height min 2.03m- Width min 1.12mClear exit stairwell signa

11、ge(Handrails both sides if over 1.85m)21Emergency EgressIlluminated Exit signs with 90min battery back up22Emergency Power & LightingEmergency generator to support all FLS services + minimal operations.Enough fuel for 48 hours continuous operationFuel supply can be shared with the boilers23Emergency

12、 Power & LightingFront & back of house:Emergency lighting connected to essential power supply with 90 min battery back upGuestrooms:1 light in the entry connected to essential power supply24Extinguishing SystemsGuestroom Sidewall Sprinklers:Quick response and no more than 150mm from the ceiling25Ext

13、inguishing SystemsBathrooms & toilets greater than 5 Sq M need to have sprinklersComputer rooms, MATV rooms, ELV Rooms etc. need to have sprinklersPre Action System26Extinguishing SystemsSprinkler system 25mm test valve and 50mm flush valve after the flow switch on each floor27Extinguishing SystemsSprinkler main and jockey pump auto startDirect read flow test meter28Extinguishing SystemsKitchen Hood & exhaust systemsANSUL29Extinguishing SystemsLaundry chute sprinkler system30Extinguishing SystemsHose/Hydrant stationsLike this Not this!

展开阅读全文
相关资源
相关搜索
资源标签

当前位置:首页 > 经管营销 > 企业管理

本站链接:文库   一言   我酷   合作


客服QQ:2549714901微博号:文库网官方知乎号:文库网

经营许可证编号: 粤ICP备2021046453号世界地图

文库网官网©版权所有2025营业执照举报